Tripping characteristic Manual Motor Starter MS 450 22...32A

30.01.2002 - production, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for ...
433KB Größe 8 Downloads 273 Ansichten
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.

a

M40 001

Tripping characteristic Manual Motor Starter MS 450 22...32A Tripping class 10 Freigegeben: 30-01-02 KlWi

Geprüft: 30-01-02 GuNi

Zust. Stelle: STO/CLP

1SA M40 0501 F 0004

Tripping characteristic with three pole load and two pole load based at cold state at any setting. With three pole load and two pole load and currents higher than 3 times of current setting the tolerance of the tripping time is +-20%. DIN VDE 0165, IEC 60079-14, EN 50019+A1...A5.

Overload release

The tripping time of the short-circuit release and the damage curve of the overload release are based on the max. rated operational current. Maximum permissable fuse if the rated short-circuit breaking capacity is exceeded

three pole load

two pole load

Damage curve of

Seconds

Tripping time

Tripping time

Die Weitergabe und Vervielfältigung dieser Unterlage, sowie die Verwertung und Mitteilung ihres Inhaltes ist nicht gestattet, soweit nicht ausdrücklich zugestanden. Zuwiderhandlungen verpflichten zu Schadenersatz. Alle Rechte vorbehalten, besonders für den Fall der Patenterteilung oder OEM-Eintragung.

Overload release

Multiples of current setting

three pole load

two pole load

3x 4x 5x 6x 7,2x 8x

31,0 sec. 17,4 sec. 11,5 sec. 8,5 sec. 5,9 sec. 4,8 sec.

25,0 sec. 14,5 sec. 9,5 sec. 6,8 sec. 4,8 sec. 3,9 sec.

Multiples of current setting

Short-circuit release